Table 10N — Other Problems/Malfunctions (Continued)

Description/

Probable Cause/Remedy

Malfunction

 

 

 

SMM

Check that PSIO communication plugs are connected correctly. Check SMM com-

Communications

munication plug. Check for proper SMM power supply. See Control Modules sec-

Failure

tion.

 

 

 

High Oil

Check for proper oil level (too much oil). Check that TXV valve is operating prop-

Temperature

erly.

While Running

 

 

 

Blank LID Screen

Increase contrast potentiometer. See Figure 42. Check red LED on LID for proper

operation, (power supply). If LED is blinking, but green LED’s are not, replace LID

 

module, (memory failure).

 

 

‘‘Communications

LID is not properly addressed to the PSIO. Make sure that ‘‘Attach to Network

Failure’’

Device,’’ ‘‘Local Device’’ is set to read the PSIO address. Check LED’s on PSIO. Is

Highlighted

red LED operating properly? Are green LED’s blinking? See control module trou-

bleshooting section.

Message At

 

Bottom of LID

 

Screen

 

 

 

Controls Test

Press the ‘‘Stop’’ pushbutton. The PIC must be in the OFF mode for the controls

test to operate. Clear all alarms. Check line voltage percent on Status01 screen.

Disabled

The percent must be within 90% to 110%. Check voltage input to SMM, calibrate

 

starter voltage potentiometer for accuracy.

 

 

Vanes Will Not

Low pressure alarm is active. Put machine into pumpdown mode or equalize pres-

Open In Control

sure. Check guide vane actuator wiring.

Test

 

 

 

Oil Pump Does

Check oil pump voltage supply. Cooler vessel pressure under vacuum. Pressurize

Not Run

vessel. Check temperature overload cutout switch.

 

 

Page 300
Image 300
Carrier PC211 High Oil, While Running Blank LID Screen, ‘‘Communications, Failure’’, Highlighted, Message At