Table 10N — Other Problems/Malfunctions (Continued)
Description/ | Probable Cause/Remedy | |
Malfunction | ||
| ||
|
| |
SMM | Check that PSIO communication plugs are connected correctly. Check SMM com- | |
Communications | munication plug. Check for proper SMM power supply. See Control Modules sec- | |
Failure | tion. | |
| ||
|
| |
High Oil | Check for proper oil level (too much oil). Check that TXV valve is operating prop- | |
Temperature | erly. | |
While Running |
| |
|
| |
Blank LID Screen | Increase contrast potentiometer. See Figure 42. Check red LED on LID for proper | |
operation, (power supply). If LED is blinking, but green LED’s are not, replace LID | ||
| module, (memory failure). | |
|
| |
‘‘Communications | LID is not properly addressed to the PSIO. Make sure that ‘‘Attach to Network | |
Failure’’ | Device,’’ ‘‘Local Device’’ is set to read the PSIO address. Check LED’s on PSIO. Is | |
Highlighted | red LED operating properly? Are green LED’s blinking? See control module trou- | |
bleshooting section. | ||
Message At | ||
| ||
Bottom of LID |
| |
Screen |
| |
|
| |
Controls Test | Press the ‘‘Stop’’ pushbutton. The PIC must be in the OFF mode for the controls | |
test to operate. Clear all alarms. Check line voltage percent on Status01 screen. | ||
Disabled | The percent must be within 90% to 110%. Check voltage input to SMM, calibrate | |
| starter voltage potentiometer for accuracy. | |
|
| |
Vanes Will Not | Low pressure alarm is active. Put machine into pumpdown mode or equalize pres- | |
Open In Control | sure. Check guide vane actuator wiring. | |
Test |
| |
|
| |
Oil Pump Does | Check oil pump voltage supply. Cooler vessel pressure under vacuum. Pressurize | |
Not Run | vessel. Check temperature overload cutout switch. | |
|
|