Example 8 — Service2 Display Screen

To access this display from the LID default screen:

1.Press MENU.

2.Press SERVICE.

3.Scroll down to highlight EQUIPMENT SERVICE.

4.Press SELECT.

5.Scroll down to highlight SERVICE2.

6.Press SELECT.

Table 2, Example 8 — Service2 Display Screen

Description

Configurable

Units

Reference

Default

Point

Range

Value

 

 

Name

 

 

 

 

 

 

 

 

 

OPTIONS BOARD 1

20mA POWER CONFIGURA- TION External = 0, Internal = 1

RESET 20 mA Power Source

DISABLE/ENABLE

 

res 20 ma

DISABLE

 

 

 

 

 

 

 

 

 

 

 

20 ma

 

DEMAND 20 mA Power Source

DISABLE/ENABLE

 

dem

 

 

DISABLE

SPARE ALERT ENABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disable = 0, Low = 1, High = 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp = Alert Threshold

0-2

 

chws

 

 

 

 

 

en

0

CHWS Temp Enable

 

 

 

 

 

 

CHWS Temp Alert

–40-245 (–40-118)

DEG F (DEG C)

chws

 

 

 

 

 

al

245 (118)

CHWR Temp Enable

0-2

 

chwr

 

 

 

 

 

en

0

CHWR Temp Alert

–40-245 (–40-118)

DEG F (DEG C)

chwr

 

 

 

 

 

al

245 (118)

Reset Temp Enable

0-2

 

rres

 

 

en

0

Reset Temp Alert

–40-245 (–40-118)

DEG F (DEG C)

rres

 

 

al

245 (118)

Spare Temp 1 Enable

0-2

 

spr1

 

 

 

en

0

Spare Temp 1 Alert

–40-245 (–40-118)

DEG F (DEG C)

spr1

 

 

 

al

245 (118)

Spare Temp 2

Enable

0-2

 

spr2

 

 

 

en

0

Spare Temp 2

Alert

–40-245 (–40-118)

DEG F (DEG C)

spr2

 

 

 

al

245 (118)

Spare Temp 3

Enable

0-2

 

spr3

 

 

 

en

0

Spare Temp 3

Alert

–40-245 (–40-118)

DEG F (DEG C)

spr3

 

 

 

al

245 (118)

Page 261
Image 261
Carrier PC211 specifications Example 8 Service2 Display Screen