Legend For Table 10, A - N
1CR AUX | — | Compressor Start Contact | OILPD | — | Oil Pressure | ||||||
CA P | — | Compressor Current | OILT | — | Oil Sump Temperature | ||||||
CDFL | — | Condenser Water Flow | PIC |
|
|
|
|
| — | Product Integrated Control | |
CHIL S S | — | Chiller Start/Stop | PRS |
|
|
| TRIP | — | Pressure Trip Contact | ||
CMPD | — | Discharge Temperature | PSIO | — Processor Sensor Input/Output Module | |||||||
CRP | — | Condenser Pressure | RLA |
|
|
|
|
| — | Rated Load Amps | |
ERT | — | Evaporator Refrigerant Temperature | RUN |
|
|
|
| AUX | — | Compressor Run Contact | |
EVFL | — | Chilled Water Flow | SPR |
|
|
| PL | — Spare Protective Limit Input | |||
GV TRG | — | Target Guide Vane Position | SMM | — | Starter Management Module | ||||||
LID | — | Local Interface Device | STR |
|
|
| FLT | — | Starter Fault | ||
MTRB | — | Bearing Temperature | TXV |
|
|
|
|
| — | Thermostatic Expansion Valve | |
MTRW | — | Motor Winding Temperature | V |
| P | — | Line Voltage: Percent | ||||
| V REF | — Voltage Reference |
Table 10A — Shutdown with | ||
|
|
|
Primary Message | Secondary Message | Probable Cause/Remedy |
|
|
|
Manually Stopped — | CCN or Local to Start | PIC in OFF mode, press the CCN or |
Press |
| local softkey to start unit. |
|
|
|
Terminate Pumpdown | To Select CCN or Local | Enter the Control Test table and |
Mode |
| select Terminate Lockout to unlock |
|
| compressor. |
|
|
|
Shutdown In Progress | Compressor Unloading | Machine unloading before shutdown |
|
| due to Soft Stop feature. |
|
|
|
Shutdown In Progress | Compressor Deenergized | Machine compressor is being com- |
|
| manded to stop. Water pumps are |
|
| deenergized within one minute. |
|
|
|
Ice Build | Operation Complete | Machine shutdown from Ice Build |
|
| operation. |
|
|
|