Table 2, Example 8 — Service2 Display Screen (Continued)

Description

Configurable

Units

Reference

Default

Point

Range

Value

 

 

Name

 

 

 

 

 

 

 

 

 

OPTIONS BOARD 2

20mA POWER CONFIGURA- TION External = 0, Internal = 1

SPARE 1 20 mA Power Source

DISABLE/ENABLE

 

sp1

20 ma

DISABLE

 

 

 

 

 

 

20 ma

 

SPARE 2 20 mA Power Source

DISABLE/ENABLE

 

sp2

DISABLE

SPARE ALERT ENABLE

 

 

 

 

 

 

 

 

Disable = 0, Low = 1, High = 2

 

 

 

 

 

 

 

 

Temp = Alert Threshold

0-2

 

spr4

 

 

en

0

Spare Temp 4 Enable

 

 

Spare Temp 4 Alert

–40-245 (–40-118)

DEG F (DEG C)

spr4

 

 

al

245 (118)

Spare Temp 5 Enable

0-2

 

spr5

 

 

en

0

Spare Temp 5 Alert

–40-245 (–40-118)

DEG F (DEG C)

spr5

 

 

al

245 (118)

Spare Temp 6 Enable

0-2

 

spr6

 

 

en

0

Spare Temp 6 Alert

–40-245 (–40-118)

DEG F (DEG C)

spr6

 

 

al

245 (118)

Spare Temp 7 Enable

0-2

 

spr7

 

 

en

0

Spare Temp 7 Alert

–40-245 (–40-118)

DEG F (DEG C)

spr7

 

 

al

245 (118)

Spare Temp 8

Enable

0-2

 

spr8

 

 

en

0

Spare Temp 8

Alert

–40-245 (–0-118)

DEG F (DEG C)

spr8

 

 

al

245 (118)

Spare Temp 9

Enable

0-2

 

spr9

 

 

en

0

Spare Temp 9

Alert

–40-245 (–40-118)

DEG F (DEG C)

spr9

 

 

al

245 (118)

Note: This screen provides the means to generate alert messages based on exceeding the ‘‘Temp Alert’’ threshold for each point listed. If the ‘‘Enable’’ is set to 1, a value above the ‘‘Temp Alert’’ threshold shall generate an alert message. If the ‘‘Enable’’ is set to 2, a value below the ‘‘Temp Alert’’ threshold shall generate an alert message. If the ‘‘Enable’’ is set to 0, alert generation is disabled.