CAUTION ! CAUTION
Damage to the starter may result if wires are reversed.
If problem is still not resolved, consult the starter manufacturer for servicing.
Testing Silicon Control Rectifiers (SCRs) in
To check for a shorted SCR refer to Steps
1.Connect ohmmeter across terminals L1 and T1. Check the resistance reading. Resistance reading should be greater than 10,000 ohms.
Click here for Figure 46 — Typical Benshaw, Inc.
2.Connect ohmmeter across terminals L2 and T2. Check the resistance reading. Resistance reading should be greater than 10,000 ohms.
3.Connect ohmmeter across terminals L3 and T3. Check the resistance reading. Resistance reading should be greater than 10,000 ohms.
If the SCRs tested were not defective, but the problem persists, refer to Steps