
Table 13 — Cutler-Hammer ® Solid-State Starter Troubleshooting Guide
Problem | Probable Cause | Area of Correction | |
|
|
| |
CB trips (electrically | Motor is not connected. | Connect motor to starter. | |
operated disconnecting |
|
| |
Incorrect phase sequence to the starter, 3- | Switch two incoming power leads. The 50 | ||
means opens) as it is | |||
phase power not connected, or terminal | and 51 corresponding motor leads must | ||
closed. | |||
loose. | also be switched to maintain the same | ||
| |||
|
| motor rotation. | |
|
|
| |
| Shorted SCR. | Perform shorted SCR check. | |
|
|
| |
| Shunt trip contact between terminals closes | Perform shorted SCR check. | |
| due to shorted SCR. |
| |
|
|
| |
| Shunt trip latching relay not reset (if used). | Reset STR relay by pushing RESET but- | |
|
| ton on relay. | |
|
|
| |
CB trips while motor is | Microprocessor detected | Check wiring to logic module or replace | |
running. | operation. | logic module. | |
|
|
| |
CB trips when STOP is | Voltage drop across SCR (looks like | Check SCR. | |
pressed. | shorted SCR). |
| |
|
|
| |
Starter does not pick up | Line voltage is not applied. | Check incoming lines for proper voltage. | |
and maintain. |
|
| |
Overload is not reset. | Reset overload. | ||
| |||
|
|
| |
| 120 v control voltage is not present. | Check control transformer fuse. Check | |
|
| control circuits. | |
|
|
| |
| Heatsink overtemperature switches are | Check for continuity through overtemper- | |
| open. | ature switches. Check that all fans are | |
|
| rotating freely. Check for excessive motor | |
|
| current draw. | |
|
|
| |
Starter maintains but | Current limit is too low. | Increase current limit setting clockwise. | |
motor does not acceler- |
| Set ramp time to minimum (counterclock- | |
ate or does not attain |
| wise). | |
full speed (stalls). |
|
| |
|
|
| |
Insufficient Torque. | Improper current feedback. | Check current feedback resistor for | |
|
| proper calibration. | |
|
|
| |
| High breakaway torque required. | Load is not suitable for reduced voltage | |
|
| starting. | |
|
|
| |
Motor accelerates too | Current limit is too low. | Increase current limit setting clockwise. | |
slowly. |
|
| |
Ramp time is too long. | Decrease ramp time setting counterclock- | ||
| |||
|
| wise. | |
|
|
| |
| Broken current feedback resistor. | Check by recalibrating CFR. | |
|
|
|