Example 13 — Maintenance (Maint04) Display Screen

To access this display from the LID default screen:

1.Press MENU.

2.Press SERVICE.

3.Scroll down to highlight CONTROL ALGORITHM STATUS.

4.Press SELECT.

5.Scroll down to highlight MAINT04.

6.Press SELECT.

Table 2, Example 13 — Maintenance (Maint04) Display Screen

Description

Range/Status

Units

Reference

Point Name

 

 

 

 

 

 

 

 

 

 

 

 

LEAD/LAG: Configuration

DISABLE,LEAD,LAG,STANDBY, INVALID

 

leadlag

Current Mode

DISABLE,LEAD,LAG,STANDBY, CONFIG

 

llmode

Load Balance Option

DISABLE/ENABLE

 

loadbal

LAG Start Time

0-60

MIN

lagstart

LAG Stop Time

0-60

MIN

lagstop

Prestart Fault Time

0-30

MIN

preflt

Pulldown: Delta T/Min

x.xx

Δ DEG F (ΔDEG C)

pull

 

 

dt

Satisfied?

No/Yes

 

pull

 

 

sat

LEAD CHILLER in Control

No/Yes

 

leadctrl

LAG CHILLER: Mode

Reset,Off,Local,CCN

 

lagmode

Run Status

Timeout,Recycle,Startup,Ramping,Running

 

lagstat

 

Demand,Override,Shutdown,Abnor-

 

 

 

 

 

 

 

 

mal,Pumpdown

 

 

 

 

 

 

 

Start/Stop

Stop,Start,Retain

 

lag

 

s s

 

 

 

 

 

 

 

 

Recovery Start Request

No/Yes

 

lag

 

rec

STANDBY CHILLER: Mode

Reset,Off,Local,CCN

 

stdmode

Run Status

Timeout,Recycle,Startup,Ramping,Running

 

stdstat

 

Demand,Override,Shutdown,Abnor-

 

 

mal,Pumpdown

 

 

 

 

 

 

 

Start/Stop

Stop,Start,Retain

 

std

 

s s

 

 

 

 

 

 

 

 

Recovery Start Request

No/Yes

 

std

 

rec

 

 

 

 

 

 

 

 

 

Notes:

1.Only values with capital letter reference point names are variables available for read operation. Forcing is not supported on this maintenance screen.

2.The MAINT04 screen is available on PSIO Software Version 09 and higher.

3.Δ = delta degrees.