19XL PIC SERVICE1 TABLE CONFIGURATION SHEET

DESCRIPTION

RANGE

UNITS

DEFAULT

VALUE

 

 

 

 

 

 

Motor Temp Override

150 to

200

DEG F

200

 

(66 to

93)

(DEG C)

(93)

 

 

 

 

 

 

 

 

 

Cond Pressure Override

150 to

245

psig

195

 

(1034 to

1639)

(1345)

 

(kPa)

 

 

[90 to 200 (620 to 1379)]

[125 (862)]

 

 

 

 

 

 

 

 

 

 

Refrig Override Delta T

2 to

5

DEG F

3

 

(1 to

3)

(DEG C)

(1.6)

 

 

 

 

 

 

 

 

Chilled Medium

Water/Brine

 

Water

 

 

 

 

 

 

Brine Refrig Trippoint

8 to 40

DEG F

33

 

(±13.3 to 4)

(DEG C)

(1)

 

 

 

 

 

 

 

 

 

Compr Discharg Alert

125 to

200

DEG F

200

 

(52 to

93)

(DEG C)

(93)

 

 

 

 

 

 

 

 

 

Bearing Temp Alert

175 to

185

DEG F

175

 

(79 to

85)

(DEG C)

(79)

 

 

 

 

 

 

 

 

Water Flow Verify Time

0.5 to 5

MIN

5

 

 

 

 

 

 

Oil Press Verify Time

15 to 300

SEC

15

 

 

 

 

 

 

 

Water/Brine Deadband

0.5 to

2.0

DEG F

1.0

 

(0.3 to

1.1)

(DEG C)

(0.6)

 

 

 

 

 

 

 

 

Recycle Restart Delta T

2.0 to 10

DEG F

5

 

(1.1 to

5.5)

(DEG C)

(2.8)

 

 

 

 

 

 

 

 

 

Surge Limit/HGBP Option

0/1

 

 

0

 

Surge=0/HGBP=1

 

 

 

 

 

 

 

 

 

 

 

 

 

Surge/HGBP Delta T1

0.5 to 15

DEG F

1.5

 

(0.3 to

8.3)

(DEG C)

(0.8)

 

 

 

 

 

 

 

 

Surge/HGBP Delta P1

50 to 170

psi

75

 

(345 to 1172)

(517)

 

(kPa)

 

 

[30 to 170 (206 to 1172)]

[50 (345)]

 

 

 

 

 

 

 

 

 

Surge/HGBP Delta T2

0.5 to 15.0

DEG F

10

 

(0.3 to

8.3)

(DEG C)

(5.6)

 

 

 

 

 

 

 

 

Surge/HGBP Delta P2

50 to 170

psi

170

 

(345 to 1172)

(1172)

 

(kPa)

 

 

[30 to 170 (206 to 1172)]

[85 (586)]

 

 

 

 

 

 

 

 

 

 

Surge/HGBP Deadband

1 to

3

DEG F

1

 

(0.6 to

1.6)

(DEG C)

(0.6)

 

 

 

 

 

 

 

 

 

Surge Delta Percent Amps

10 to

50

%

25

 

 

 

 

 

 

 

Surge Time Period

1 to

5

MIN

2

 

 

 

 

 

 

 

Demand Limit Source

0/1

 

 

0

 

Amps=0/Load=1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Amps Correction Factor

1 to

8

 

3

 

 

 

 

 

 

 

NOTE: Values in [ ] indicate HFC-134a values, if this refrigerant is con®gured in the Control Test.

CL-7

Page 387