To Prevent Accidental Start-Up
The PIC can be set up so that sta rt-up of the unit is more di ff ic u lt than just pressing th e
LOCAL or CCN softkeys during machine service or when necessary. By accessing the
Status01 table, and hi ghl ighting the chiller Star t /Stop line, the value ca n be ov e rridden to stop
by pressing SELECT and then the STOP and ENTER softkeys. ‘‘SUPVSR’’ will appear after the
value. When attempting to restart, remember to release the override. The default machine
message line will also state that the St art/Stop has been set to ‘‘Start’’ or ‘‘ Stop’’ when the value
is overridden.
Check Machine Operating Condition
Check to be sure that machin e temperatures, pres s ur es , water flows, and oil and ref rigerant
levels indicate that the system is functioning properly.
Instruct the Customer Operator
Check to be sure that the operator(s) understand all operating and maintenance procedures.
Point out the various machine parts and explain their function as part of the complete system.
Cooler-Condenser
Float chamber, relief devices, refrigerant ch arging valve, tem perature sensor locations,
pressure transducer loc a tions, Schrader fitt in gs, waterboxes and tub es, and vents and drains.