If surge prevention occu rs too soon or too late:
Modify Amp Correcti on Fa ct o rs
To modify the amp correction factor, use the v alues listed in Table 7. Enter the appr opr i ate
amp correction fact or in t he Service1 table of Equip ment Service.
Modify Equipment Configuration If Necessary
The Equipment Config uration table has tabl es to select and view or mo dify. Carrier’s cert ified
drawings will have the con figuration values req uired for the jobsite. Mod ify these tables only if
requested.
Load Surge Prevention Occu rs
Too Soon Surge Prevention
Occurs Too Late
At low loads (<50%) Increase P1 by 1 0 psid (70 kPad) Decrease P1 by 10 psid
(70 kPad)
At high loads (>50%) Increase P2 by 1 0 psid (70 kPad) Decrease P2 by 10 psid
(70 kPad)
Click here fo r Table 7 — Am ps Correction Fac tors for 19XL M otors