Transfer Refrigerant from Storage Tank to Machine

1.Equalize refrigerant pressure.

a.Use the Control Test Terminate Lockout to turn on water pumps and monitor pressures.

b.Close pumpout/storage tank valves 2, 4, 5, and 8, and close machine charging valve 7; open machine isolation valves 11, 12, 13, and 14 (if present).

c.Open pumpout/storage tank valves 3 and 6, open machine valves 1a and 1b.

Valve

1a

1b

2

3

4

5

6

7

8

11

12

13

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Condition

 

 

C

 

C

C

 

C

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Click here for Figure 36 — 19XL Pumpout Unit Wiring Schematic

Click here for Figure 37 — Optional Pumpout System

d.Gradually crack open valve 5 to increase machine pressure to 68 psig (469 kPa) for HCFC-22, 35 psig (141 kPa) for HFC-134a. Slowly feed refrigerant to prevent freeze up.