Table 10N — Other Problems/Malfunctions
Description/ | Probable Cause/Remedy | |
Malfunction | ||
| ||
|
| |
| Chilled water set point set too high. Access set point on LID and verify. | |
| Capacity override or excessive cooling load (machine at design capacity). Check | |
| LID status messages. Check for outside air infiltration into conditioned space. | |
| Condenser temperature too high. Check for proper flow, examine cooling tower | |
Chilled Water/Brine | operation, check for air or water leaks, check for fouled tubes. | |
Refrigerant level low. Check for leaks, add refrigerant, and trim charge. | ||
Temperature Too | ||
Liquid bypass in waterbox. Examine division plates and gaskets for leaks. | ||
High (Machine | ||
Guide vanes fail to open. Use Control Test to check operation. | ||
Running) | ||
Chilled water control point too high. Access control algorithm status and check | ||
| ||
| chilled water control operation. | |
| Guide vanes fail to open fully. Be sure that the guide vane target is released. | |
| Check guide vane linkage. Check limit switch in actuator. Check that sensor is in | |
| the proper terminals. | |
|
| |
Chilled Water/Brine | Chilled water set point set too low. Access set point on LID and verify. | |
Chilled water control point too low. Access control algorithm status and check | ||
Temperature Too | chilled water control for proper resets. | |
Low (Machine | High discharge temperature keeps guide vanes open. | |
Running) | Guide vanes fail to close. Be sure that guide vane target is released. Check chilled | |
| water sensor accuracy. Check guide vane linkage. Check actuator operation. | |
|
| |
Chilled Water | Deadband too narrow. Configure LID for a larger deadband. | |
Proportional bands too narrow. Either INC or DEC proportional bands should be | ||
Temperature | increased. | |
Fluctuates. Vanes | Loose guide vane drive. Adjust chain drive. | |
Hunt | Defective vane actuator. Check through Control Test. | |
| Defective temperature sensor. Check sensor accuracy. | |
|
| |
Low Oil Sump | Check for proper oil level (not enough oil). Check for proper refrigerant level (too | |
Temperature | much refrigerant). | |
While Running |
| |
(Less than 100 F |
| |
[38 C]) |
| |
|
| |
At Power Up, | Check for proper communications wiring on PSIO module. Check that the COMM1 | |
Default Screen | communications wires from the LID are terminated to the COMM1 PSIO connec- | |
Does Not Appear, | tion. | |
| ||
‘‘Tables Loading’’ |
| |
Message |
| |
Continually |
| |
Appears |
| |
|
|