* [LIMIT] is shown on the LID as the temperature, pre ssu re, voltage, etc., set po int predefined or select ed
by the operator as an over r ide , alert, or alarm condi ti on. [VALUE] is the actual t emperature, pressu r e,
voltage, etc., at which t he control tripped.
Table 10I — Normal Run Overrides Active (Alerts)
Primary Message Secondary Messa ge Alarm Message/Primary
Cause Additional Cause/
Remedy
Run Capacity Lim-
ited High Condenser Pres-
sure CRP [VALUE]* exceeded limi t of
[LIMIT]*. Condenser pressure
override. See Capacity Ov er-
rides, Table 4. Cor rect
operating condition,
modify setpoint, or
release override.
Run Capacity Lim-
ited High Motor Temperatu re MTRW [VALUE]* exceeded limit of
[LIMIT]*. Motor temperature over-
ride.
Run Capacity Lim-
ited Low Evap Refrig Temp ERT [VALUE]* exceeded li mit of
[LIMIT]*. Check refrigerant charge
level.
Run Capacity Lim-
ited High Compressor Lift Surge Prevention Over ride; lift too
high for compressor.
Run Capacity Lim-
ited Manual Guide Vane T ar-
get GV TRG Run Capacity Li mited:
Manual guide vane targ et.