Example 5 — Configuration (Config) Display Screen

To access this display from the LID default screen:

1.Press MENU.

2.Press SERVICE.

3.Scroll down to highlight EQUIPMENT CONFIGURATION.

4.Press SELECT.

5.Scroll down to highlight CONFIG.

6.Press SELECT.

Table 2, Example 5 — Configuration (Config) Display Screen

Description

Configurable

Units

Reference

Default

Range

Point Name

Value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RESET TYPE 1

–30-30 (–17-17)

 

 

 

 

 

 

 

20ma

10Δ(6Δ)

Degrees Reset at 20 mA

DEG F (DEG C)

deg

 

RESET TYPE 2

–40-245 (–40-118)

 

res

 

rt1

85 (29)

Remote Temp (No Reset)

DEG F (DEG C)

Remote Temp (Full Reset)

–40-245 (–40-118)

DEG F (DEG C)

res

 

rt2

65 (18)

Degrees Reset

–30-30 (–17-17)

DEG F (DEG C)

res

 

rt

10Δ (6Δ)

RESET TYPE 3

0-15 (0-8)

 

restd

 

1

10Δ (6Δ)

CHW Delta T (No Reset)

DEG F (DEG C)

CHW Delta T (Full Reset)

0-15 (0-8)

DEG F (DEG C)

restd

 

2

0Δ (-0Δ)

Degrees Reset

–30-30 (–17-17)

DEG F (DEG C)

deg

 

chw

5Δ (3Δ)

Select/Enable Reset Type

0-3

 

res

 

sel

0

ECW CONTROL OPTION

DISABLE/ENABLE

 

ecw

 

opt

DISABLE

 

 

 

 

 

 

 

20ma

 

Demand Limit At 20 mA

40-100

%

dem

 

40

20mA Demand Limit Option

DISABLE/ENABLE

 

dem

 

sel

DISABLE

Auto Restart Option

DISABLE/ENABLE

 

astart

DISABLE

Remote Contacts Option

DISABLE/ENABLE

 

r contact

DISABLE

 

 

 

 

 

 

 

ramp

 

Temp Pulldown Deg/Min

2-10

 

tmp

 

3

Load Pulldown %/Min

5-20

 

kw ramp

10

 

 

 

 

 

 

 

 

 

Select Ramp Type:

0/1

 

ramp opt

1

Temp = 0, Load = 1

 

 

 

 

 

 

 

 

 

 

 

0-99

 

ldsgrp

0

Loadshed Group Number

 

Loadshed Demand Delta

0-60

%

ldsdelta

20

Maximum Loadshed Time

0-120

MIN

maxldstm

60

CCN Occupancy Config:

3-99

 

occpcxxe

3

Schedule Number

 

Broadcast Option

DISABLE/ENABLE

 

occbrcst

DISABLE

ICE BUILD Option

DISABLE/ENABLE

 

ibopt

 

 

DISABLE

ICE BUILD TERMINATION

0-2

 

ibterm

0

0 =Temp, 1 =Contacts, 2 =Both

 

ICE BUILD Recycle Option

DISABLE/ENABLE

 

ibrecyc

DISABLE

 

 

 

 

 

 

 

 

 

 

 

 

Note: Δ = delta degrees.