Example 5 — Configuration (Config) Display Screen
To access this display from the LID default screen:
1.Press MENU.
2.Press SERVICE.
3.Scroll down to highlight EQUIPMENT CONFIGURATION.
4.Press SELECT.
5.Scroll down to highlight CONFIG.
6.Press SELECT.
Table 2, Example 5 — Configuration (Config) Display Screen
Description | Configurable | Units | Reference | Default | ||||||||
Range | Point Name | Value | ||||||||||
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
RESET TYPE 1 |
|
|
|
|
|
|
| 20ma | 10Δ(6Δ) | |||
Degrees Reset at 20 mA | DEG F (DEG C) | deg |
| |||||||||
RESET TYPE 2 |
| res |
| rt1 | 85 (29) | |||||||
Remote Temp (No Reset) | DEG F (DEG C) | |||||||||||
Remote Temp (Full Reset) | DEG F (DEG C) | res |
| rt2 | 65 (18) | |||||||
Degrees Reset | DEG F (DEG C) | res |
| rt | 10Δ (6Δ) | |||||||
RESET TYPE 3 |
| restd |
| 1 | 10Δ (6Δ) | |||||||
CHW Delta T (No Reset) | DEG F (DEG C) | |||||||||||
CHW Delta T (Full Reset) | DEG F (DEG C) | restd |
| 2 | 0Δ | |||||||
Degrees Reset | DEG F (DEG C) | deg |
| chw | 5Δ (3Δ) | |||||||
Select/Enable Reset Type |
| res |
| sel | 0 | |||||||
ECW CONTROL OPTION | DISABLE/ENABLE |
| ecw |
| opt | DISABLE | ||||||
|
|
|
|
|
|
| 20ma |
| ||||
Demand Limit At 20 mA | % | dem |
| 40 | ||||||||
20mA Demand Limit Option | DISABLE/ENABLE |
| dem |
| sel | DISABLE | ||||||
Auto Restart Option | DISABLE/ENABLE |
| astart | DISABLE | ||||||||
Remote Contacts Option | DISABLE/ENABLE |
| r contact | DISABLE | ||||||||
|
|
|
|
|
|
| ramp |
| ||||
Temp Pulldown Deg/Min |
| tmp |
| 3 | ||||||||
Load Pulldown %/Min |
| kw ramp | 10 | |||||||||
|
|
|
|
|
|
|
|
| ||||
Select Ramp Type: | 0/1 |
| ramp opt | 1 | ||||||||
Temp = 0, Load = 1 |
|
|
|
|
|
|
|
|
|
|
| |
| ldsgrp | 0 | ||||||||||
Loadshed Group Number |
| |||||||||||
Loadshed Demand Delta | % | ldsdelta | 20 | |||||||||
Maximum Loadshed Time | MIN | maxldstm | 60 | |||||||||
CCN Occupancy Config: |
| occpcxxe | 3 | |||||||||
Schedule Number |
| |||||||||||
Broadcast Option | DISABLE/ENABLE |
| occbrcst | DISABLE | ||||||||
ICE BUILD Option | DISABLE/ENABLE |
| ibopt |
|
| DISABLE | ||||||
ICE BUILD TERMINATION |
| ibterm | 0 | |||||||||
0 =Temp, 1 =Contacts, 2 =Both |
| |||||||||||
ICE BUILD Recycle Option | DISABLE/ENABLE |
| ibrecyc | DISABLE | ||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
Note: Δ = delta degrees.