Table 10H — Normal Run with Reset, Temperature, or Demand
Primary Message Secondary Message Probable Cause/Rem ed y
Running — Reset Active 4-20MA Signal
Reset program active based u pon Config table
setup.
Running — Reset Active Remote Sensor Control
Running — Reset Active CHW Temp Difference
Running — Temp
Control
Leaving Chilled Water Default method of tempera ture control.
Running — Temp
Control
Entering Chilled Water ECW control activated on Config table.
Running — Temp
Control
Temperature Ramp Loading Ramp loading in effect. Us e Service1 table to
modify.
Running — Demand
Limited
By Demand Ramp Loading Ramp loading in effect. Use Service1 table to
modify.
Running — Demand
Limited
By Local Demand Setpoint Demand limit setpo int is < actual demand.
Running — Demand
Limited
By 4-20MA Signal
Demand limit is active b ased on Config table
setup.
Running — Demand
Limited
By CCN Signal
Running — Demand
Limited
By LoadShed/Redline
Running — Temp
Control
Hot Gas Bypass Hot Gas Bypass is energized. See Surge Preven-
tion in the Control section.
Running — Demand
Limited
By Local Signal Active demand limit manual ly overridden or
Status01 table.
Running — Temp
Control
Ice Build Mode Machine is running under Ic e Build temperature
control.