Operation Features:
•2 chiller lead/lag
•addition of a third chiller for backup
•manual rotation of lead chiller
•load balancing if configured
•staggered restart of the chillers after a power failure
•chillers may be piped in parallel or in series chilled water flow
Common Point Sensor Installation
Lead/lag operation does not require a common chilled water point sensor. Common point
sensors can be added to the
Note: If the common point sensor option is chosen on a chilled water system, both machines should have their own
When installing chillers in series, a common point sensor should be used. If a common point sensor is not used, the leaving chilled water sensor of the upstream chiller must be moved into the leaving chilled water pipe of the downstream chiller.
If return chilled water control is required on chillers piped in series, the common point return