5.Oil reservoir temperature is above 140 F (60 C) or refrigerant temperature plus 50° F (28° C).

6.Valves in the evaporator and condenser water circuits are open.

Note: If pumps are not automatic, make sure water is circulating properly.

7.Solid-state starter checks: The Power +15 and the Phase Correct LEDs must be lit before the starter will energize. If the Power +15 LED is not on, incoming voltage is not present or is incorrect. If the Phase Correct LED is not lit, rotate any 2 incoming phases to correct the phasing.

WARNING ! WARNING

Do not permit water or brine that is warmer than 110 F (43 C) to flow through the cooler or condenser. Refrigerant overpressure may discharge through the relief devices and result in the loss of refrigerant charge.

8.Press RELEASE to automate the chiller start/stop value on the Status01 table to enable the chiller to start. The initial factory setting of this value is overridden to stop in order to prevent accidental start-up.

Page 170