5.Oil reservoir temperature is above 140 F (60 C) or refrigerant temperature plus 50° F (28° C).
6.Valves in the evaporator and condenser water circuits are open.
Note: If pumps are not automatic, make sure water is circulating properly.
7.
WARNING ! WARNING
Do not permit water or brine that is warmer than 110 F (43 C) to flow through the cooler or condenser. Refrigerant overpressure may discharge through the relief devices and result in the loss of refrigerant charge.
8.Press RELEASE to automate the chiller start/stop value on the Status01 table to enable the chiller to start. The initial factory setting of this value is overridden to stop in order to prevent accidental