5. Oil reservoir tempe r at ure is above 140 F (60 C) or refrig erant temperature pl us 50° F
(28° C).
6. Valves in the evapora to r and condenser water circ u its are open.
Note: If pumps are not automati c , mak e sure water is circulatin g properly.
7. Solid-state starter checks: The Power +15 and the Phase Correct LEDs must be lit before
the starter will ene r giz e . If the Power +15 LED is not on, incoming voltage is not pre sent or
is incorrect. If the Ph as e Co rrect LED is not lit, rota te any 2 incoming phases to cor r ec t the
phasing.
8. Press RELEASE to automate the chiller start/stop value on the Status01 table to enable the
chiller to start. The initial factory set ting of this value is overr idden to stop in order t o prevent
accidental start-u p.
Do not permit water or br in e t h at is warmer than 110 F (43 C) to flow through the
cooler or condenser . Re frigerant overpressu re may discharge thro ug h the relief
devices and result in th e loss of refrigerant cha rg e.
WARNING !WARNING