Table 10B — Timing Out or Timed Out
Primary Message | Secondary Message | Probable Cause/Remedy |
|
|
|
Ready To Start In XX Min | Unoccupied Mode | Time schedule for PIC is unoccupied. Machines will start |
|
| only when occupied. |
|
|
|
Ready To Start In XX Min | Remote Contacts Open | Remote contacts have stopped machine. Close contacts to |
|
| start. |
|
|
|
Ready To Start In XX Min | Stop Command In | Chiller START/STOP on Status01 manually forced to stop. |
| Effect | Release value to start. |
|
|
|
Ready To Start In XX Min | Recycle Restart Pend- | Machine in recycle mode. |
| ing |
|
|
|
|
Ready To Start | Unoccupied Mode | Time schedule for PIC is UNOCCUPIED. Machine will start |
|
| when occupied. Make sure the time and date have been |
|
| set on the Service menu. |
|
|
|
Ready To Start | Remote Contacts Open | Remote contacts have stopped machine. Close contacts to |
|
| start. |
|
|
|
Ready To Start | Stop Command In | Chiller START/STOP on Status01 manually forced to stop. |
| Effect | Release value to start. |
|
|
|
Ready To Start In XX Min | Remote Contacts | Machine timer counting down unit. Ready for start. |
| Closed |
|
|
|
|
Ready To Start In XX Min | Occupied Mode | Machine timer counting down unit. Ready for start. |
|
|
|
Ready To Start | Remote Contacts | Machine timers complete, unit start will commence. |
| Closed |
|
|
|
|
Ready To Start | Occupied Mode | Machine timers complete, unit start will commence. |
|
|
|
Startup Inhibited | Loadshed In Effect | CCN loadshed module commanding chiller to stop. |
|
|
|
Ready To Start In XX Min | Start Command In | Chiller START/STOP on Status01 has been manually |
| Effect | forced to start. Machine will start regardless of time sched- |
|
| ule or remote contact status. |
|
|
|