Table 10K — Machine Protect Limit Faults
WARNING ! WARNING
Excessive numbers of the same fault can lead to severe machine damage.
Seek service expertise.
Primary | Secondary | Alarm Message/ | Additional Cause/Remedy | |||
Message | Message | Primary Cause | ||||
| ||||||
|
|
|
|
|
| |
| High Discharge | CMPD [VALUE] | Check discharge temperature immedi- | |||
| Temp | exceeded limit of | ately. Check sensor for accuracy; check | |||
Protective |
| [LIMIT]*. Check dis- | for proper condenser flow and tempera- | |||
| charge temperature. | ture; check oil reservoir temperature. | ||||
Limit |
| |||||
|
|
|
| Check condenser for fouled tubes or air in | ||
|
|
|
|
| ||
|
|
|
|
| machine. Check for proper guide vane | |
|
|
|
|
| actuator operation. | |
|
|
|
|
|
| |
Protective | Low Refrigerant | ERT [VALUE] exceed | Check for proper amount of refrigerant | |||
Temp | limit of [LIMIT]*. Check | charge; check for proper water flow and | ||||
Limit |
| evap pump and flow | temperatures. Check for proper guide | |||
|
| switch. | vane actuator operation. | |||
|
|
|
|
|
| |
| High Motor Temper- | MTRW [VALUE] | Check motor temperature immediately. | |||
Protective | ature | exceeded limit of | Check sensor for accuracy. Check for | |||
| [LIMIT]*. Check motor | proper condenser flow and temperature. | ||||
Limit |
| cooling and solenoid. | Check motor cooling system for restric- | |||
|
|
|
|
| tions. Check motor cooling solenoid for | |
|
|
|
|
| proper operation. Check refrigerant filter. | |
|
|
|
|
|
| |
| High Bearing Tem- | MTRB [VALUE] | Check for throttled oil supply isolation | |||
Protective | perature | exceeded limit of | valves. Valves should be wide open. | |||
| [LIMIT]*. Check oil cool- | Check oil cooler thermal expansion valve. | ||||
Limit |
| ing control. | Check sensor accuracy. Check journal | |||
|
|
|
|
| and thrust bearings. Check refrigerant fil- | |
|
|
|
|
| ter. Check for excessive oil sump level. | |
|
|
|
|
|
| |
| Low Oil Pressure | OILPD [VALUE] | Check power to oil pump and oil level. | |||
|
| exceeded limit of | Check for dirty filters or oil foaming at | |||
Protective |
| [LIMIT]*. Check oil pump | ||||
| and transducer. | out. Reduce ramp load rate if foaming | ||||
Limit |
| |||||
|
|
|
| noted. | ||
|
|
|
|
| ||
|
|
|
|
| Note: This alarm is not related to pressure | |
|
|
|
|
| switch problems. | |
|
|
|
|
|
| |
Protective | No Motor Current | CA P Loss of Motor Cur- | Check wiring: Check torque setting on | |||
|
|
|
|
| ||
| rent: Check sensor. | solid state starter. Check for main circuit | ||||
Limit |
|
|
|
| breaker trip. Check power supply to PSIO | |
|
|
|
|
| module. | |
|
|
|
|
|
| |