Carrier PC211 specifications Surge/HGBP Delta P2

Models: PC211

1 392
Download 392 pages 38.23 Kb
Page 260
Image 260

Table 2, Example 7 — Service1 Display Screen (Continued)

Description

Configurable

Units

Reference

Default Value

Point

Range

 

 

Name

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Surge/HGBP Delta P2

[30-170 (207-1172)]

PSI (kPa)

hgb

 

dp2

170 (1172) [85 (586)]

Full Load Points (T2/P2)

1-3 (0.6-1.6)

DEG F (DEG C)

hgb

 

dp

1 (0.6)

Surge/HGBP Deadband

Surge Delta Percent Amps

10-50

%

surge

 

 

a

25

Surge Time Period

1-5

MIN

surge

 

 

t

2

Demand Limit Source

0/1

 

dem

 

 

src

0

Select: Amps=0, Load=1

1-8

 

corfact

3

Amps Correction Factor

 

Motor Rated Load Amps

1-9999

AMPS

a

fs

 

 

 

200

Motor Rated Line Voltage

1-9999

VOLTS

v

 

fs

 

 

 

460

Meter Rated Line KW

1-9999

kW

kw

 

 

 

 

fs

600

Line Frequency

0/1

HZ

freq

 

 

 

0

Select: 0=60 Hz, 1=50 Hz

REDUCE/FULL

 

starter

REDUCE

Compr Starter Type

 

Condenser Freeze Point

–20-35 (–28.9-1.7)

DEG F (DEG C)

cdfreeze

34 (1)

Soft Stop Amps Threshold

40-100

%

softstop

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note:

1.Condenser Freeze Point and Softstop Amps Threshold are only selectable/readable on PSIO Software Versions 09 and higher.

2.Values in [ ] indicate HFC-134a values.

3.Δ = delta degrees.