Config Table Modifications

Change the values in this table per job data. See certified drawings for values. Modifications include:

chilled water reset

entering chilled water control (Enable/Disable)

4-20 mA demand limit

auto restart option (Enable/Disable)

remote contact option (Enable/Disable)

Owner-Modified CCN Tables

The following tables are described for reference only.

Occdef Table Modifications — The Occdef tables contain the Local and CCN time schedules, which can be modified here, or in the Schedule screen as described previously.

Holidef Table Modifications —The Holidef tables configure the days of the year that holidays are in effect. See the holiday paragraphs in the Controls section for more details.

Brodefs Table Modifications — The Brodefs screen defines the outside-air temperature sensor and humidity sensor if one is to be installed. It will define the start and end of daylight savings time. Enter the dates for the start and end of daylight savings if required for the location. Brodefs also will activate the Broadcast function which enables the holiday periods that are defined on the LID.

Other Tables —The Alarmdef, Cons-def, and Runt-def contain tables for use with a CCN