The starting torque potentiometer should be set so that when the PIC calls for the motor to start, the rotor should just start to turn. The nominal dial position for a 60 Hz motor is approximately the 11:30 position. The nominal dial position for a 50 Hz motor is approxi- mately in the 9:30 position because the board is turned on its side, so that the 9:00 o’clock position is located where the 6:00 o’clock position would normally be located. The ramp potentiometer should be set so that the motor is up to full speed in 15 to 20 sec- onds, the bypass contactors have energized, and the auxiliary LCD is energized.

7.Proceed to apply power to the starter.

8.The Power +15 and Phase Correct LEDs should be on. If not, see the starter Troubleshooting Guide section.

Click here for Figure 30 — Benshaw, Inc. Solid-State Starter Power Stack

Click here for Figure 31 — Ramp Up and Starting Torque Potentiometers