5. Protect the system from damage during shutdown periods.
6. Maintain the set point , time schedules, and oth er P IC functions.
Prepare the Machine for Start-Up
Follow the steps described in the Initial Start-Up section.
To Start the M a chine
1. Start the water pumps , if th ey are not automatic.
2. On the LID default screen, press the LOCAL or CCN softkey to start the system. If the
machine is in the OCCUPI E D m od e, and the start timers ha v e ex pi red, the start sequen c e
will start. Follow the procedure described in the Start-Up/Shutdown/Recycle section.
Check the Running System
After the compressor s t arts, the operator shou ld m on itor the LID display an d obs e rve the
parameters for n ormal operati ng conditions:
1. The oil reservoir tem per a ture should be above 140 F (60 C) during shutdown, an d above
100 F (38 C) during compressor operation.
2. The bearing oil temper at ure accessed on the Sta tu s01 table should be 120 to 165 F (49 to
74 C). If the bearing tem per a ture reads more than 18 0 F (83 C) with the oil pump runnin g,
stop the mach ine and determ ine the cause of the high te mperature.

Do not restart

the
machine until corrected.