Table 2 — LID Screens
Notes:
1.Only 12 lines of information appear on the LID screen at any given time. Press NEXT or PREVIOUS to highlight a point or to view points below or above the current screen.
2.The LID may be configured in English or SI units, as required, through the LID configuration screen.
3.Data appearing in the Reference Point Names column is used for CCN operations only.
4.All options associated with ICE BUILD, Lead/Lag, CCN Occupancy Configuration, and Soft Stopping are only available on PSIO Software Version 9 and higher.
Example 1 — Status01 Display Screen
To access this display from the LID default screen:
1.Press MENU.
2.Press STATUS (STATUS01 will be highlighted).
3.Press SELECT.
Table 2, Example 1 — Status01 Display Screen
Description | Range | Units | Reference Point | |||
Name (Alarm | ||||||
|
|
| History) | |||
|
|
|
|
|
|
|
Control Mode | Reset.Off.Local.CCN |
| MODE | |||
Run Status | Timeout.Recycle.Startup. |
| STATUS | |||
| Ramping.Running.Demand. |
|
|
|
|
|
| Override.Shutdown.Abnormal. |
|
|
|
|
|
| Pumpdown |
|
|
|
|
|
Occupied? | No/Yes |
| OCC |
|
| |
Alarm State | Normal/Alarm |
| ALM |
|
| |
*Chiller Start/Stop | Stop/Start |
| CHIL | S S | ||
Base Demand Limit | % | DLM |
|
| ||
*Active Demand Limit | % | DEM |
| LIM | ||
Compressor Motor Load | % | CA |
| L |
| |
Current | % | CA |
| P | ||
Amps | AMPS | CA |
| A | ||
*Target Guide Vane Pos |
|
|
|
| TRG | |
% | GV |
| ||||
Actual Guide Vane Pos | % | GV |
| ACT | ||
Water/Brine: Setpoint | DEG F (DEG C) | SP |
|
| ||
* Control Point | DEG F (DEG C) | LCW |
| STPT | ||
|
|
|
|
|
|
|