Table 10F —
Primary | Secondary | Alarm Message/Primary | Additional Cause/Remedy | |||||
Message | Message | Cause | ||||||
| ||||||||
|
|
|
|
|
|
|
| |
Failure To | Starter Transi- | RUN AUX Starter Transition | Check starter for proper operation. Run | |||||
|
|
|
|
|
|
| ||
tion Fault | Fault: Check 1CR/1M/Interlock | contact failed to close. | ||||||
Start | ||||||||
| mechanism. |
| ||||||
|
|
| ||||||
|
|
|
|
|
|
|
| |
Failure To | 1CR AUX Con- | 1CR AUX Starter Contact | Check starter for proper operation. Start | |||||
|
|
|
|
|
|
| ||
tact Fault | Fault: Check 1CR/1M aux. con- | contact failed to close. | ||||||
Start | ||||||||
| tacts. |
| ||||||
|
|
| ||||||
|
|
|
|
|
|
| ||
Failure To | Motor Amps Not | CA P Motor Amps Not Sensed: | Check for proper motor amps signal to | |||||
|
|
|
|
| ||||
Sensed | Check motor load signal. | SMM. Check wiring from SMM to cur- | ||||||
Start |
|
|
|
|
|
| rent transformer. Check main motor cir- | |
|
|
|
|
|
|
| cuit breaker for trip. | |
|
|
|
|
|
| |||
| Check Refriger- | Current Refrigerant Properties | Pressures at transducers indicate | |||||
Failure To | ant Type | Abnormal — Check Selection of | another refrigerant type in Control Test. | |||||
| refrigerant type | Make sure to access the ATTACH TO | ||||||
Start |
| |||||||
|
|
|
|
|
| NETWORK DEVICE table after chang- | ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| ing refrigerant type. | |
|
|
|
| |||||
| Low Oil Pressure | Low Oil Pressure [LIMIT]: | The oil pressure differential switch is | |||||
|
| Check oil pressure switch/ | open when the compressor tried to | |||||
Failure To |
| pump and 2C aux. | START. Check the switch for proper | |||||
|
|
|
|
|
| operation. Also, check the oil pump | ||
Start |
|
|
|
|
|
| ||
|
|
|
|
|
| interlock (2C aux) in the power panel | ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| and the high condenser pressure | |
|
|
|
|
|
|
| switch. | |
|
|
|
|
|
|
|
| |
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.