Table 10F — Start-Up Failures: This is an alarm condition. A manual reset is required to clear. (Continued)

Primary

Secondary

Alarm Message/Primary

Additional Cause/Remedy

Message

Message

Cause

 

 

 

 

 

 

 

 

 

Failure To

Starter Transi-

RUN AUX Starter Transition

Check starter for proper operation. Run

 

 

 

 

 

 

 

tion Fault

Fault: Check 1CR/1M/Interlock

contact failed to close.

Start

 

mechanism.

 

 

 

 

 

 

 

 

 

 

 

 

Failure To

1CR AUX Con-

1CR AUX Starter Contact

Check starter for proper operation. Start

 

 

 

 

 

 

 

tact Fault

Fault: Check 1CR/1M aux. con-

contact failed to close.

Start

 

tacts.

 

 

 

 

 

 

 

 

 

 

 

Failure To

Motor Amps Not

CA P Motor Amps Not Sensed:

Check for proper motor amps signal to

 

 

 

 

 

Sensed

Check motor load signal.

SMM. Check wiring from SMM to cur-

Start

 

 

 

 

 

 

rent transformer. Check main motor cir-

 

 

 

 

 

 

 

cuit breaker for trip.

 

 

 

 

 

 

 

Check Refriger-

Current Refrigerant Properties

Pressures at transducers indicate

Failure To

ant Type

Abnormal — Check Selection of

another refrigerant type in Control Test.

 

refrigerant type

Make sure to access the ATTACH TO

Start

 

 

 

 

 

 

 

NETWORK DEVICE table after chang-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ing refrigerant type.

 

 

 

 

 

Low Oil Pressure

Low Oil Pressure [LIMIT]:

The oil pressure differential switch is

 

 

Check oil pressure switch/

open when the compressor tried to

Failure To

 

pump and 2C aux.

START. Check the switch for proper

 

 

 

 

 

 

operation. Also, check the oil pump

Start

 

 

 

 

 

 

 

 

 

 

 

 

interlock (2C aux) in the power panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and the high condenser pressure

 

 

 

 

 

 

 

switch.

 

 

 

 

 

 

 

 