Table 10G — Compressor Jumpstart and Refrigerant Protection
Primary Message | Secondary | Alarm Message/Primary | Additional Cause/Remedy | |||
Message | Cause | |||||
|
| |||||
|
|
|
|
|
| |
| Unit Should Be | CA P Emergency: Compres- | Compressor is running with | |||
Unauthorized | Stopped | sor running without control | more than 10% RLA and control | |||
| authorization. | is trying to shut it down. Throw | ||||
Operation |
|
|
|
| power off to compressor if | |
|
|
|
|
| unable to stop. Determine cause | |
|
|
|
|
| before repowering. | |
|
|
|
|
|
| |
Potential Freeze- | Evap Press/Temp | ERT Emergency: | Determine cause. If pumping | |||
Too Low | prevention. | refrigerant out of machine, stop | ||||
up |
|
|
|
| operation and go over pumpout | |
|
|
|
|
| procedures. | |
|
|
|
|
|
| |
| Disconnect Power | RUN AUX Emergency: DIS- | Starter and run and start con- | |||
|
|
|
|
|
| |
Failure To Stop |
| CONNECT POWER. | tacts are energized while control | |||
|
|
|
| tried to shut down. Disconnect | ||
|
|
|
|
| ||
|
|
|
|
| power to starter. | |
|
|
|
|
|
| |
Loss Of | With Starter | Loss of Communication with | Check wiring from PSIO to | |||
| Starter: Check machine. | SMM. Check SMM module trou- | ||||
Communciation |
| |||||
|
|
|
| bleshooting procedures. | ||
|
|
|
|
| ||
|
|
|
|
|
| |
Starter Contact | Abnormal 1CR or Run | 1CR AUX Starter Contact | Starter run and start contacts | |||
|
|
|
|
| ||
Aux | Fault: Check 1CR/1M aux. | energized while machine was | ||||
Fault | ||||||
| contacts. | off. Disconnect power. | ||||
|
| |||||
|
|
|
|
|
| |
| Cond Press/Temp | CRT [VALUE] exceeded limit | The condenser pressure trans- | |||
| Too Low | of [LIMIT]* Emergency: | ducer is reading a pressure that | |||
|
| could freeze the water in the | ||||
Potential Freeze |
|
|
|
| condenser tubes. Check for con- | |
|
|
|
| denser refrigerant leaks, bad | ||
Up |
|
|
|
| ||
|
|
|
| transducers, or transferred | ||
|
|
|
|
| ||
|
|
|
|
| refrigerant. Place the unit in | |
|
|
|
|
| Pumpdown mode to eliminate | |
|
|
|
|
| ALARM if vessel is evacuated. | |
|
|
|
|
|
|
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.