DO NOT VENT refrigerant relief devices within a building. Outlet from rupture
disc or relief valve mu st b e v e nte d outdoors in accord an ce with the latest edition
of ANSI/ASHRAE 15 (Am erican National Stand ar ds Institute/Americ an Society of
Heating, Refrigeration, and Air Conditioning Engineers). The accumulation of
refrigerant in an en closed space can displac e oxygen and cause asphy xi ation.
PROVIDE a d equate ve ntilation in accorda nc e with ANSI /ASHRAE 1 5 , especiall y
for enclosed and low overhead spaces. Inhalation of high concentrations of
vapor is harmful and may cause heart irregularities, unconsciousness, or death.
Misuse can be fatal. Va po r i s heavier than air and redu ces the amount of oxygen
available for breathing. Product causes eye and skin irritation. Decomposition
products are hazard ous.
DO NOT USE OXYGEN to purge lines or to pressur ize a machine for any purp ose.
Oxygen gas reacts violently with oil, grease, and other common substances.
NEVER EXCEED specified test pressures. VERIFY the allowable test pressure by
checking the instr uc tion literature and th e de sign pressures on the eq ui p ment
nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry nitrogen.
DO NOT VALVE OFF any safe ty device.
BE SURE that all pressure relief devices are properly installed and functioning
before operating any mac hin e.