refrigerant setting. Press EXIT softkey to leave the screen without changes.

To Change Refrigerant Type

Enter the Controls Test tables on the Service Menu. See Figure 17. Select REFRIGERANT TYPE. The screen will display the current refrigerant setting. Press YES softkey to change the current setting. Next, move to the ATTACH TO NETWORK DEVICE screen on the Service menu and the ATTACH TO LOCAL DEVICE to upload the new refrigerant tables.

Input Service Configurations

The following configurations require the LID screen to be in the Service portion of the menu.

password

input time and date

LID configuration

controller identification

service parameters

equipment configuration

automated control test

Password

When accessing the Service tables, a password must be entered. All LIDs are initially set for a password of 1-1-1-1. This password may be changed in the LID configuration screen, if desired.

Page 154
Image 154
Carrier PC211 specifications To Change Refrigerant Type, Password