Configure SERVICE1 Table
Access Service1 table to modify/view the following to jobsite parameters:
Note: Other values are left at the de fault values. These may be c ha nged by the operator as
required. Servi ce2 and Service 3 tables can be modified by the owner/operator a s
required.
Modify Minimum and Maximum Load Points (T1/P1; T2/P2) If Necessary
These pairs of machine loa d points, located on the Se r v ic e1 table, determine when to lim it
guide vane travel or to open the ho t gas bypass valve when surge prevent ion is needed. Thes e
points should be set base d on individual machine op erating conditions .
Chilled Medium
Brine Refrigerant Trippoint
Surge Limiting or
Hot Gas Bypass Option
Minimum Load Points (T1/P1)
Maximum Load Points (T2/ P2)
Amps Correction Factor
Motor Rated Load Am ps
Motor Rated Line V oltage
Motor Rated Line kW
Line Frequency
Compressor Starter Type
Water or Brine?
Usually 3° F (1.7° C) below design refrige rant temperature
Is HGBP installed?
Per job data — See Modify Load Point s section (this page)
Per job data — See Modify Load Point s section (this page)
See Table 6
Per job data
Per job data
Per job data (if kW met er installed)
50 or 60 Hz
Reduced voltage or full ?