19XL PIC CONFIG TABLE CONFIGURATION SHEET
DESCRIPTION | RANGE | UNITS | DEFAULT | VALUE |
|
|
|
|
|
RESET TYPE 1 |
|
|
|
|
|
|
|
|
|
Degrees Reset at 20 mA | ±30 to 30 | DEG F | 10 |
|
(±17 to 17) | (DEG C) | (6) |
| |
|
| |||
|
|
|
|
|
RESET TYPE 2 |
|
|
|
|
|
|
|
|
|
Remote Temp (No Reset) | ±40 to 245 | DEG F | 85 |
|
(±40 to 118) | (DEC C) | (29) |
| |
|
| |||
|
|
|
|
|
Remote Temp (Full Reset) | ±40 to 245 | DEG F | 65 |
|
(±40 to 118) | (DEG C) | (18) |
| |
|
| |||
|
|
|
|
|
Degrees Reset | ±30 to 30 | DEG F | 10 |
|
(±17 to 17) | (DEG C) | (6) |
| |
|
| |||
|
|
|
|
|
RESET TYPE 3 |
|
|
|
|
|
|
|
|
|
CHW Temp (No Reset) | 0 to 15 | DEG F | 10 |
|
(0 to 8) | (DEG C) | (6) |
| |
|
| |||
|
|
|
|
|
CHW Temp (Full Reset) | 0 to 15 | DEG F | 0 |
|
(0 to 8) | (DEG C) | (0) |
| |
|
| |||
|
|
|
|
|
Degrees Reset | ±30 to 30 | DEG F | 5 |
|
(±17 to 17) | (DEG C) | (3) |
| |
|
| |||
|
|
|
|
|
Select/Enable Reset Type | 0 to 3 |
| 0 |
|
|
|
|
|
|
ECW Control Option | Disable/Enable |
| Disable |
|
|
|
|
|
|
Demand Limit at 20 mA | 40 to 100 | % | 40 |
|
|
|
|
|
|
20 mA Demand Limit Option | Disable/Enable |
| Disable |
|
|
|
|
|
|
Auto Restart Option | Disable/Enable |
| Disable |
|
|
|
|
|
|
Remote Contacts Option | Disable/Enable |
| Disable |
|
|
|
|
|
|
Temp Pulldown Deg/Min | 2 to 10 |
| 3 |
|
|
|
|
|
|
Load Pulldown %/Min | 5 to 20 |
| 10 |
|
|
|
|
|
|
Select Ramp Type: | 0/1 |
| 1 |
|
Temp=0/Load=1 |
|
| ||
|
|
|
| |
|
|
|
|
|
Loadshed Group Number | 0 to 99 |
| 0 |
|
|
|
|
|
|
Loadshed Demand Delta | 0 to 60 | % | 20 |
|
|
|
|
|
|
Maximum Loadshed Time | 0 to 120 | Min | 60 |
|
|
|
|
|
|
CCN Occupancy Con®g: | 3 to 99 |
| 3 |
|
Schedule Number |
|
| ||
|
|
|
| |
|
|
|
|
|
CCN Occupancy Con®g: | Disable/Enable |
| Disable |
|
Broadcast Option |
|
| ||
|
|
|
| |
|
|
|
|
|
ICE BUILD Option | Disable/Enable |
| Disable |
|
|
|
|
|
|
ICE BUILD TERMINATION: | 0, 1, 2 |
| 0 |
|
0 =Temp, 1 =Contacts, 2 =Both |
|
| ||
|
|
|
| |
|
|
|
|
|
ICE BUILD RECYCLE Option | Disable/Enable |
| Disable |
|
|
|
|
|
|