Table 13 — Cutler-Hammer ® Solid-State Starter Troubleshooting Guide (Continued)
Problem | Probable Cause | Area of Correction | |
|
|
| |
Overload relay trips | Incorrect heater coils (melting allow). | Check heater coil rating. | |
when starting. |
|
| |
Loose heater coil. | Tighten heater coil. | ||
| |||
|
|
| |
| Long starting time (high inertia applications | Motor and starter thermal capabilities | |
| may require slow trip overload and oversize | must be evaluated before extending over- | |
| starter). | load trip times. | |
|
|
| |
| Mechanical problems. | Check machinery for binding or exces- | |
|
| sive loading. | |
|
|
| |
| Single phasing. | See ‘‘Starter or motor is noisy or vibrates | |
|
| when starting’’ symptom in troubleshoot- | |
|
| ing table. | |
|
|
| |
| Excessive starting time (current limit may | Increase current limit setting clockwise. | |
| be set too low). |
| |
|
|
| |
Overload relay trips | Incorrect heater coils (melting alloy). | Check heater coil rating. | |
when running. |
|
| |
Mechanical problems. | Check machinery for binding or exces- | ||
| |||
|
| sive loading. | |
|
|
| |
| Single phasing. | See ‘‘Starter or motor is noisy or vibrates | |
|
| when starting’’ problem in troubleshooting | |
|
| table. | |
|
|
| |
Heatsink overtempera- | Excessive current. | Check motor current draw. | |
ture switch opens. |
|
| |
Defective heatsink, fan. | Check that all fans are rotating freely. | ||
| |||
|
|
| |
Erratic operation. | Loose connections. | Check all connections. | |
|
|
|
Legend
CCW — Counter Clockwise
CFR — Current Feedback Resistor
STR — Shunt Trip Relay