Carrier PC211 Ordering Replacement Chiller Parts, Optional Pumpout Safety Control Settings Figure

Models: PC211

1 392
Download 392 pages 38.23 Kb
Page 218
Image 218

Optional Pumpout Safety Control Settings (Figure 40)

The optional pumpout system high-pressure switch should open at 220 ± 5 psig (1517 ±

34 kPa) and should reset automatically on pressure drop to 190 psig (1310 kPa) for HCFC-22

machines. For machines using HFC-134a, the switch opens at 161 psig (1110 kPa) and closes

at 130 psig (896 kPa). Check the switch setting by operating the pumpout compressor and

slowly throttling the pumpout condenser water.

Click here for Figure 40 — Optional Pumpout System Controls

Ordering Replacement Chiller Parts

When ordering Carrier specified parts, the following information must accompany an order:

machine model number and serial number

name, quantity, and part number of the part required

delivery address and method of shipment.

Page 218
Image 218
Carrier PC211 specifications Ordering Replacement Chiller Parts, Optional Pumpout Safety Control Settings Figure