Check Relief Devices
Be sure that relief devic e s have been piped to the outd oors in compliance wit h th e latest
edition of ANS I/ASHRAE Standa rd 15 and applic able local sa fety codes. Pipin g connections
must allow for access to the valve mechanis m for periodic inspection and leak testing.
19XL relief valves are set to relieve at the 300 psig ( 206 8 kPa) machine design pre ssure.
Inspect Wiring
1. Examine wiring for con formance to job wiring dia grams and to all applicabl e electrical
codes.
Do not check voltage supply without proper equipment and precautions. Serious
injury may result. Follow power company recommendations.
WARNING !WARNING
CAUTION CAUTION
!
Do not apply an y kind of test v oltage, even for a rotation check, if the machine i s
under a dehydration vacuum. Insulation breakdown and serious damage may
result.