If the Motor Rotation Is Not Clockwise (as viewed through the sight glass), reverse any 2 of the 3 incoming power leads to the starter and recheck rotation.
Note:
CAUTION ! CAUTION
Do not check motor rotation during coastdown. Rotation may have reversed dur- ing equalization of vessel pressures.
Click here for Figure 34 — Correct Motor Rotation
Notes on
1.When the compressor is energized to start by the 1CR relay, confirm that the Relay On LED is lit on the starter SCR control board. The compressor motor should start to turn immediately when this light comes on. If not, adjust the start torque potentiometer in a clockwise direction.
2.Observe that all