Table 10K — Machine Protect Limit Faults (Continued)
WARNING ! WARNING
Excessive numbers of the same fault can lead to severe machine damage.
Seek service expertise.
Primary | Secondary | Alarm Message/ | Additional Cause/Remedy | |||||
Message | Message | Primary Cause | ||||||
| ||||||||
|
|
|
|
|
|
|
| |
Protective | Power Loss | V |
| P Power Loss: Check |
| |||
Limit |
| voltage supply. |
| |||||
|
|
|
|
|
|
| Check | |
Protective | Low Line Voltage | V P [VALUE] exceeded | ||||||
|
|
|
|
|
| adjust potentiometer if necessary. Check | ||
| limit of [LIMIT]*. Check | |||||||
Limit |
| |||||||
| voltage supply. | transformers to SMM. Check power to | ||||||
|
| |||||||
|
|
|
|
|
|
| PSIO module. Check distribution bus. | |
| High Line Voltage | V P [VALUE] exceeded | ||||||
Protective | Consult power company. | |||||||
|
|
|
|
|
| |||
| limit of [LIMIT]*. Check | |||||||
Limit |
|
| ||||||
| voltage supply. |
| ||||||
|
|
| ||||||
|
|
|
|
|
|
| ||
Protective | Low Chilled Water | EVFL Flow Fault: Check |
| |||||
Limit | Flow | evap pump/flow switch. | Perform pumps Control Test and verify | |||||
|
|
|
|
|
|
| proper switch operation. Check all water | |
Protective | Low Condenser | CDFL Flow Fault: Check | valves and pump operation. | |||||
Limit | Water Flow | cond pump/flow switch. |
| |||||
|
|
|
|
|
|
| ||
| High Condenser | High Cond Pressure | Check the | |||||
Protective | Pressure | [OPEN]: Check switch, | for proper condenser pressures and con- | |||||
| 2C aux., and water temp/ | denser waterflow. Check for fouled tubes. | ||||||
Limit |
| flow. | Check the 2C aux. contact and the oil | |||||
|
|
|
|
|
|
| pressure switch in the power panel. This | |
|
|
|
|
|
|
| alarm is not caused by the transducer. | |
|
|
|
|
|
|
| ||
Protective | High Condenser | High Cond Pressure | Check water flow in condenser. Check for | |||||
Pressure | [VALUE]: Check switch, | fouled tubes. Transducer should be | ||||||
Limit |
| water flow, and trans- | checked for accuracy. This alarm is not | |||||
|
| ducer. | caused by the high pressure switch. | |||||
|
|
|
|
|
|
| ||
Protective | 1CR Aux Contact | CR AUX Starter Contact | 1CR auxiliary contact opened while | |||||
|
|
|
|
|
|
| ||
Fault | Fault: Check 1CR/1M aux | machine was running. Check starter for | ||||||
Limit | ||||||||
| contacts. | proper operation. | ||||||
|
| |||||||
|
|
|
|
|
|
| ||
Protective | Run Aux Contact | RUN AUX Starter Con- | Run auxiliary contact opened while | |||||
|
|
|
|
|
|
| ||
Fault | tact Fault: Check 1CR/1M | machine was running. Check starter for | ||||||
Limit | ||||||||
| aux contacts. | proper operation. | ||||||
|
| |||||||
|
|
|
|
|
|
|
| |