Table 10K — Machine Protect Limit Faults (Continued)

WARNING ! WARNING

Excessive numbers of the same fault can lead to severe machine damage.

Seek service expertise.

Primary

Secondary

Alarm Message/

Additional Cause/Remedy

Message

Message

Primary Cause

 

 

 

 

 

 

 

 

 

Protective

Power Loss

V

 

P Power Loss: Check

 

Limit

 

voltage supply.

 

 

 

 

 

 

 

 

Check 24-vdc input sensor on the SMM;

Protective

Low Line Voltage

V P [VALUE] exceeded

 

 

 

 

 

 

adjust potentiometer if necessary. Check

 

limit of [LIMIT]*. Check

Limit

 

 

voltage supply.

transformers to SMM. Check power to

 

 

 

 

 

 

 

 

 

PSIO module. Check distribution bus.

 

High Line Voltage

V P [VALUE] exceeded

Protective

Consult power company.

 

 

 

 

 

 

 

limit of [LIMIT]*. Check

Limit

 

 

 

voltage supply.

 

 

 

 

 

 

 

 

 

 

 

Protective

Low Chilled Water

EVFL Flow Fault: Check

 

Limit

Flow

evap pump/flow switch.

Perform pumps Control Test and verify

 

 

 

 

 

 

 

proper switch operation. Check all water

Protective

Low Condenser

CDFL Flow Fault: Check

valves and pump operation.

Limit

Water Flow

cond pump/flow switch.

 

 

 

 

 

 

 

 

 

High Condenser

High Cond Pressure

Check the high-pressure switch. Check

Protective

Pressure

[OPEN]: Check switch,

for proper condenser pressures and con-

 

2C aux., and water temp/

denser waterflow. Check for fouled tubes.

Limit

 

flow.

Check the 2C aux. contact and the oil

 

 

 

 

 

 

 

pressure switch in the power panel. This

 

 

 

 

 

 

 

alarm is not caused by the transducer.

 

 

 

 

 

 

 

Protective

High Condenser

High Cond Pressure

Check water flow in condenser. Check for

Pressure

[VALUE]: Check switch,

fouled tubes. Transducer should be

Limit

 

water flow, and trans-

checked for accuracy. This alarm is not

 

 

ducer.

caused by the high pressure switch.

 

 

 

 

 

 

 

Protective

1CR Aux Contact

CR AUX Starter Contact

1CR auxiliary contact opened while

 

 

 

 

 

 

 

Fault

Fault: Check 1CR/1M aux

machine was running. Check starter for

Limit

 

contacts.

proper operation.

 

 

 

 

 

 

 

 

 

Protective

Run Aux Contact

RUN AUX Starter Con-

Run auxiliary contact opened while

 

 

 

 

 

 

 

Fault

tact Fault: Check 1CR/1M

machine was running. Check starter for

Limit

 

aux contacts.

proper operation.

 

 

 

 

 

 

 

 

 

 