Example 7 — Service1 Display Screen

To access this display from the LID default screen:

1.Press MENU.

2.Press SERVICE.

3.Scroll down to highlight EQUIPMENT SERVICE.

4.Press SELECT.

5.Scroll down to highlight SERVICE1.

6.Press SELECT.

Table 2, Example 7 — Service1 Display Screen

Description

Configurable

Units

Reference

Default Value

Point

Range

 

 

Name

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Temp Override

150-200 (66-93)

DEG F (DEG C)

mt

over

200 (93)

 

 

 

 

 

 

 

 

 

 

 

195 (1345) [125 (862)]

Cond Press Override

150-245 (1034-1689)

PSI (kPa)

cp

over

 

[90-200 (620-1379)]

 

 

 

 

 

 

 

 

 

 

3Δ (1.6Δ)

Refrig Override Delta T

2-5 (1-3)

DEG F (DEG C)

ref

 

over

Chilled Medium

Water/Brine

 

medium

WATER

Brine Refrig Trippoint

8-40 (–13.3-4)

DEG F (DEG C)

br

trip

33 (1)

 

 

 

 

 

alert

 

Compr Discharge Alert

125-200 (52-93)

DEG F (DEG C)

cd

200 (93)

 

 

 

 

 

 

 

 

 

 

 

 

Bearing Temp Alert

175-185 (79-85)

DEG F (DEG C)

tb alert

175 (79)

 

 

 

 

 

 

 

 

 

 

 

t

 

Water Flow Verify Time

0.5-5

MIN

wflow

 

 

 

5

Oil Press Verify Time

15-300

SEC

oilpr

 

 

 

t

15

Water/Brine Deadband

0.5-2.0 (0.3-1.1)

DEG F (DEG C)

cw

 

db

1.0 (0.6)

Recycle Restart Delta T

2.0-10.0 (1.1-5.6)

DEG F (DEG C)

rcyc

 

 

dt

5 (2.8)

Surge Limit/HGBP Option

0/1

 

srg

 

 

hgbp

0

Select: Surge=0, HGBP=1

0.5-15 (0.3-8.3)

DEG F (DEG C)

hgb

 

 

 

dt1

1.5 (0.8)

Surge/HGBP Delta T1

 

 

 

Surge/HGBP Delta P1

50-170 (345-1172)

PSI (kPA)

hgb

 

 

 

dp1

75 (517) [50 (345)]

 

[30-170 (207-1172)]

 

 

 

 

 

 

 

 

 

 

 

Min. Load Points (T1/P1)

0.5-15 (0.3-8.3)

DEG F (DEG C)

hgb

 

 

 

dt2

10 (5.6)

Surge/HGBP Delta T2

 

 

 

 

50-170 (345-1172)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 259