Reset Type 2 can now be act iv at ed.
3. Reset Type 3 — Automatic chill ed water temperat ure reset based on cooler temperature
difference. This typ e of reset will add ±30° F (±16° C) based on the temperature diff erence
between entering and leaving chilled water t emperature. This is th e onl y type of reset
available without t he ne ed of the number one 8-inp ut module. No wiring is req uired for this
type as it already uses the cooler water sensors .
To configure Reset Type 3, enter the chilled wate r temperature differ enc e (the difference
between entering and leaving chilled water) at which no temperature res e t occurs. This
chilled water tempe r at ure difference is usu all y the full design load tem pe rature difference.
The difference in chill ed water temperature at which the full amount of r es et will occur is
now entered on the next in put line. Next, the amo unt of reset is entered. Res et Type 3 can
now be activated.