Reset Type 2 can now be activated.
3.Reset Type 3 — Automatic chilled water temperature reset based on cooler temperature difference. This type of reset will add ±30° F (±16° C) based on the temperature difference between entering and leaving chilled water temperature. This is the only type of reset available without the need of the number one
To configure Reset Type 3, enter the chilled water temperature difference (the difference between entering and leaving chilled water) at which no temperature reset occurs. This chilled water temperature difference is usually the full design load temperature difference. The difference in chilled water temperature at which the full amount of reset will occur is now entered on the next input line. Next, the amount of reset is entered. Reset Type 3 can now be activated.