based on load rate or temp erature rate. I t is accessed on the Equip ment Configurati on,
Config table (Table 2, Example 5 ).
To Stop the Machine
1. The occupancy schedu le will start and stop the m ac h ine automatically on ce the time
schedule is set up.
2. By pressing the STOP bu tton for one second, the alar m li ght will blink once to con firm that
the button has been press e d, then the compress or wil l follow the normal shut down
sequence as described in the Controls section. The machi ne will not restart until the CCN or
LOCAL softkey is pres s ed. The machine is now in the O FF mo de . If the machine fails to
stop, in addition to ac tion that the PIC will i nitiate, the operator should close the gui de vanes
by overriding the guide vane target to zero to redu ce machine load; then by op ening the
main disconnect. Do no t attempt to stop the mac hin e by opening an isolatin g knife switch.
High intensity arcing may occur.

Do not restart

the machine until the prob lem is diagnosed
and corrected.
After Limited Shutdown
No special preparations should be necessary. Follow the regular preliminary checks and
starting procedures .