Flow Switches (Field Supplied)

Operate water pumps with machine off. Manually reduce water f low and observe switch for proper cutout.

Safety shutdown occur s wh en cutout time exceeds 3 s ec o nds.

Starter Accelerati on Time
(Determined by i nrush current
going below 100% compres-
sor motor l oad)
>45 seconds For machines with red uced voltage
mechanical and solid-state starte rs
>10 seconds For machines with full voltage starters
(Configured on Servic e1 table)
Starter Transition >75 seconds Reduced voltage starter s only
Condenser Freeze Protect ion
Energizes condenser pu mp relay if
condenser refrigerant temperature or
condenser entering wat er tempera-
ture is below the configu red con-
denser freeze point temp erature.
Deenergizes when the temperatur e is
5 F (3 C) above condenser fr eeze
point temperature.
CONDENSER FREEZE POINT config-
ured in Service01 tabl e with a default
setting of 34 F (1 C) .
Table 3 — Protective Safety Limits and Control Settings (Continued)

Monitored Parameter Limit Applicable Comments