CCW — Countercl ockwise
CW — Clockwise
Table 6 — Potentiometer Adjustment
Dial
Adjustment Range
Function Factory Setting
Minimum
(CCW) Maximum
(CW)
Starting Current 100% 400% Sets initial starting current
level. 100%
Ramp Time (Adj ust-
able Current Ramp) 2 seconds 30 seconds Sets time during which cur-
rent ramps from the ini tial
starting level to the maxi-
mum possible current limit
setting.
15 seconds
Current Limit 100% 400% Sets maximum starting cur-
rent. 250%
Pulse Start 0 (Off) 2 seconds Sets duration of 400% cur-
rent pulse. Pulse is use d to
break load free.
OFF
Current Trip 50% 400% Sets running current t rip. 175%
Power Sav er — — OFF