Table 6 — Potentiometer Adjustment

 

Adjustment Range

 

 

 

Dial

 

 

Function

 

Factory Setting

Minimum

Maximum

 

 

 

 

 

 

(CCW)

(CW)

 

 

 

 

 

 

 

 

 

Starting Current

100%

400%

Sets initial starting current

 

100%

 

 

 

level.

 

 

 

 

 

 

 

 

Ramp Time (Adjust-

2 seconds

30 seconds

Sets time during which cur-

 

15 seconds

able Current Ramp)

 

 

rent ramps from the initial

 

 

 

 

 

starting level to the maxi-

 

 

 

 

 

mum possible current limit

 

 

 

 

 

setting.

 

 

 

 

 

 

 

 

Current Limit

100%

400%

Sets maximum starting cur-

 

250%

 

 

 

rent.

 

 

 

 

 

 

 

 

Pulse Start

0 (Off)

2 seconds

Sets duration of 400% cur-

 

OFF

 

 

 

rent pulse. Pulse is used to

 

 

 

 

 

break load free.

 

 

 

 

 

 

 

 

Current Trip

50%

400%

Sets running current trip.

 

175%

 

 

 

 

 

 

Power Saver

OFF

 

 

 

 

 

 

CCW — Counterclockwise

CW — Clockwise