WARNING ! WARNING
Refrigerant Tracer
Use an environmentally acceptable refrigerant as a tracer for leak test procedures.
To Pressurize with Dry Nitrogen
Another method of leak testing is to pressurize with nitrogen only and use a soap bubble solution or an ultrasonic leak detector to determine if leaks are present. This should only be done if all refrigerant has been evacuated from the vessel.
1.Connect a copper tube from the pressure regulator on the cylinder to the refrigerant charging valve. Never apply full cylinder pressure to the pressurizing line. Follow the listed sequence.
2.Open the charging valve fully.
3.Slowly open the cylinder regulating valve.
4.Observe the pressure gage on the machine and close the regulating valve when the pressure reaches test level. Do not exceed 140 psig (965 kPa).