Table 10C — In Recycle Shutdown

Primary Message Secondary Messa ge Probable Cause/ Remedy

Recycle Restart Pending Occupied Mode Unit in recycle mode, chilled water temperature is not high
enough to start.
Recycle Restart Pending Remote Contact Closed Unit in recycle mode, chilled water temperature is not high
enough to start.
Recycle Restart Pending Start Command In
Effect Chiller START/STOP on Status01 manually forced to
start, chill water temperature is not high enough to start.
Recycle Restart Pending Ice Build Mode Machine in ICE BUILD mo de. Chilled Water/Brine Tem-
perature is satisfied for Ice Build Setpoint temperature.