To View and Change Set Points (Figure 19)
1. To view the Set Point table, at the Menu screen press SETPOINT.
2. There are 4 set points on this screen: Base Demand Limit; LCW Set Point (leaving chilled
water set point); ECW Set Point (entering chille d water set point); and IC E BUILD set point
(PSIO Software Version 09 and higher only). Only one of the chilled water set point s can be
active at one time, and t he t ype of set point is activa ted in the Service menu. I CE B UI LD is
also activated and con figured in the Servic e m enu .
3. Press NEXT or PREVIOUS to highlight the desired set point entry.
STATUS SCHEDULE SETPOINT SERVICE
NEXT PREVIOUS SELECT EXIT