Example 10 — Maintenance (Maint01) Display Screen
To access this display from the LID default screen:
1.Press MENU.
2.Press SERVICE.
3.Scroll down to highlight ALGORITHM STATUS.
4.Press SELECT.
5.Scroll down to highlight MAINT01.
Table 2, Example 10 — Maintenance (Maint01) Display Screen
Description | Range/Status | Units | Reference Point Name | ||||
|
|
|
|
|
|
|
|
CAPACITY CONTROL | DEG F (DEG C) | ctrlpt | |||||
Control Point | |||||||
Leaving Chilled Water | DEG F (DEG C) | LCW | |||||
Entering Chilled Water | DEG F (DEG C) | ECW | |||||
Control Point Error | DEG F (DEG C) | cperr | |||||
ECW Delta T | DEG F (DEG C) | ecwdt | |||||
ECW Reset | DEG F (DEG C) | ecwres | |||||
LCW Reset | DEG F (DEG C) | lcwres | |||||
Total Error + Resets | DEG F (DEG C) | error | |||||
Guide Vane Delta | % | gvd |
| TRG | |||
Target Guide Vane Pos | % | GV |
|
| |||
Actual Guide Vane Pos | % | GV |
|
| ACT | ||
Proportional Inc Band |
| gv |
| inc | |||
Proportional Dec Band |
| gv |
| dec | |||
Proportional ECW Gain |
| gv |
| ecw | |||
Water/Brine Deadband | DEG F (DEG C) | cwdb | |||||
|
|
|
|
|
|
|
|
Note: Overriding is not supported on this maintenance screen. Active overrides show the associated point in alert (*). Only values with capital letter reference point names are variables available for read opera- tion.