Example 10 — Maintenance (Maint01) Display Screen

To access this display from the LID default screen:

1.Press MENU.

2.Press SERVICE.

3.Scroll down to highlight ALGORITHM STATUS.

4.Press SELECT.

5.Scroll down to highlight MAINT01.

Table 2, Example 10 — Maintenance (Maint01) Display Screen

Description

Range/Status

Units

Reference Point Name

 

 

 

 

 

 

 

 

CAPACITY CONTROL

10-120 (–12.2-48.9)

DEG F (DEG C)

ctrlpt

Control Point

Leaving Chilled Water

–40-245 (–40-118)

DEG F (DEG C)

LCW

Entering Chilled Water

–40-245 (–40-118)

DEG F (DEG C)

ECW

Control Point Error

–99-99 (–55-55)

DEG F (DEG C)

cperr

ECW Delta T

–99-99 (–55-55)

DEG F (DEG C)

ecwdt

ECW Reset

–99-99 (–55-55)

DEG F (DEG C)

ecwres

LCW Reset

–99-99 (–55-55)

DEG F (DEG C)

lcwres

Total Error + Resets

–99-99 (–55-55)

DEG F (DEG C)

error

Guide Vane Delta

–2-2

%

gvd

 

TRG

Target Guide Vane Pos

0-100

%

GV

 

 

Actual Guide Vane Pos

0-100

%

GV

 

 

ACT

Proportional Inc Band

2-10

 

gv

 

inc

Proportional Dec Band

2-10

 

gv

 

dec

Proportional ECW Gain

1-3

 

gv

 

ecw

Water/Brine Deadband

0.5-2 (0.3-1.1)

DEG F (DEG C)

cwdb

 

 

 

 

 

 

 

 

Note: Overriding is not supported on this maintenance screen. Active overrides show the associated point in alert (*). Only values with capital letter reference point names are variables available for read opera- tion.