Table 10L — Machine Alerts
Primary | Secondary | Alarm Message/ | Additional Cause/Remedy | ||||
Message | Message | Primary Cause | |||||
| |||||||
|
|
|
|
|
|
| |
Recycle Alert | High Amps at Shut- | High Amps at Recycle: | Check that guide vanes are closing. Check | ||||
down | Check guide vane drive. | motor amps correction calibration is cor- | |||||
|
|
|
|
|
| rect. Check actuator for proper operation. | |
|
|
|
|
|
|
| |
Sensor Fault | Leaving Cond Water | Sensor Fault: Check |
| ||||
Temp | leaving condenser water |
| |||||
Alert |
| ||||||
| sensor. | Check sensor. See sensor test procedure. | |||||
|
| ||||||
|
|
|
|
|
|
| |
Sensor Fault | Entering Cond Water | Sensor Fault: Check |
| ||||
Temp | entering condenser |
| |||||
Alert |
| ||||||
| water sensor. |
| |||||
|
|
| |||||
|
|
|
|
|
|
| |
Low Oil | Check Oil Filter | Low Oil Pressure Alert: | Check oil filter. Check for improper oil level | ||||
Pressure Alert |
| Check oil. | or temperature. | ||||
|
|
|
|
|
|
| |
AutoRestart | Power Loss | V |
|
| P Power Loss: |
| |
Pending |
| Check voltage supply. |
| ||||
|
|
|
|
|
|
| |
AutoRestart | Low Line Voltage | V P [VALUE] exceeded |
| ||||
|
|
|
|
|
| ||
| limit of [LIMIT*]. Check | Check power supply if there are excessive | |||||
Pending |
| ||||||
| voltage supply. | compressor starts occurring. | |||||
|
| ||||||
|
|
|
|
| |||
AutoRestart | High Line Voltage | V P [VALUE] exceeded |
| ||||
|
|
|
|
|
| ||
| limit of [LIMIT*]. Check |
| |||||
Pending |
|
| |||||
| voltage supply. |
| |||||
|
|
| |||||
|
|
|
| ||||
| High Discharge Temp | CMPD [VALUE] | Discharge temperature exceeded the alert | ||||
Sensor Alert |
| exceeded limit of | threshold. Check entering condenser water | ||||
| [LIMIT*]. Check dis- | temperature. | |||||
|
| ||||||
|
| charge temperature. |
| ||||
|
|
|
| ||||
| High Bearing Tempera- | MTRB [VALUE] | Thrust bearing temperature exceeded the | ||||
Sensor Alert | ture | exceeded limit of | alert threshold. Check for closed valves, | ||||
| [LIMIT*]. Check thrust | improper oil level or temperatures. | |||||
|
| ||||||
|
| bearing temperature. |
| ||||
|
|
|
| ||||
Condenser | Pump Relay Energized | CRP High Condenser | Check ambient conditions. Check con- | ||||
| Pressure [LIMIT*]. | denser pressure for accuracy. | |||||
Pressure Alert |
| Pump energized to |
| ||||
|
| reduce pressure. |
| ||||
|
|
|
|
|
|
| |
|
|
|
|
|
| The machine load is too small to keep the | |
Recycle Alert |
|
|
|
|
| machine on line and there have been more | |
Excessive Recycle | Excessive recycle | than 5 restarts in 4 hours. Increase | |||||
| Starts | starts. | machine load, adjust hot gas bypass, | ||||
|
|
|
|
|
| increase RECYCLE RESTART DELTA T. | |
|
|
|
|
|
|
| |
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure, voltage, etc., at which the control tripped.