Table 10L — Machine Alerts

Primary

Secondary

Alarm Message/

Additional Cause/Remedy

Message

Message

Primary Cause

 

 

 

 

 

 

 

 

Recycle Alert

High Amps at Shut-

High Amps at Recycle:

Check that guide vanes are closing. Check

down

Check guide vane drive.

motor amps correction calibration is cor-

 

 

 

 

 

 

rect. Check actuator for proper operation.

 

 

 

 

 

 

 

Sensor Fault

Leaving Cond Water

Sensor Fault: Check

 

Temp

leaving condenser water

 

Alert

 

 

sensor.

Check sensor. See sensor test procedure.

 

 

 

 

 

 

 

 

 

Sensor Fault

Entering Cond Water

Sensor Fault: Check

 

Temp

entering condenser

 

Alert

 

 

water sensor.

 

 

 

 

 

 

 

 

 

 

 

Low Oil

Check Oil Filter

Low Oil Pressure Alert:

Check oil filter. Check for improper oil level

Pressure Alert

 

Check oil.

or temperature.

 

 

 

 

 

 

 

AutoRestart

Power Loss

V

 

 

P Power Loss:

 

Pending

 

Check voltage supply.

 

 

 

 

 

 

 

 

AutoRestart

Low Line Voltage

V P [VALUE] exceeded

 

 

 

 

 

 

 

 

limit of [LIMIT*]. Check

Check power supply if there are excessive

Pending

 

 

voltage supply.

compressor starts occurring.

 

 

 

 

 

 

 

AutoRestart

High Line Voltage

V P [VALUE] exceeded

 

 

 

 

 

 

 

 

limit of [LIMIT*]. Check

 

Pending

 

 

 

voltage supply.

 

 

 

 

 

 

 

 

 

High Discharge Temp

CMPD [VALUE]

Discharge temperature exceeded the alert

Sensor Alert

 

exceeded limit of

threshold. Check entering condenser water

 

[LIMIT*]. Check dis-

temperature.

 

 

 

 

charge temperature.

 

 

 

 

 

 

High Bearing Tempera-

MTRB [VALUE]

Thrust bearing temperature exceeded the

Sensor Alert

ture

exceeded limit of

alert threshold. Check for closed valves,

 

[LIMIT*]. Check thrust

improper oil level or temperatures.

 

 

 

 

bearing temperature.

 

 

 

 

 

Condenser

Pump Relay Energized

CRP High Condenser

Check ambient conditions. Check con-

 

Pressure [LIMIT*].

denser pressure for accuracy.

Pressure Alert

 

Pump energized to

 

 

 

reduce pressure.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The machine load is too small to keep the

Recycle Alert

 

 

 

 

 

machine on line and there have been more

Excessive Recycle

Excessive recycle

than 5 restarts in 4 hours. Increase

 

Starts

starts.

machine load, adjust hot gas bypass,

 

 

 

 

 

 

increase RECYCLE RESTART DELTA T.

 

 

 

 

 

 

 

*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure, voltage, etc., at which the control tripped.