Communications

Communication Systems

The MultiRanger is capable of communicating with most SCADA systems, PLCs, and PCs. The supported protocols are:

Modbus RTU/ASCII – base unit on RS-232 or RS-485 transport

PROFIBUS DP – optional SmartLinx® module

Allen-Bradley®1Remote I/O – optional SmartLinx module

DeviceNet® – optional SmartLinx module

Communication Ports

The MultiRanger comes with two communication ports on the base unit.

Port

Connection

Location

Interface

1

RJ-11 connector

inside enclosure on main board

RS-232

2

terminal block

terminal block

RS-485

RS-232

The RJ-11 jack connects to a laptop computer for the following:

initial setup

configuration

troubleshooting

periodic maintenance

RS-485

The RS-485 port on the terminal blocks connects into industrial communications wiring and has the following advantages:

runs communications cable farther

allows multiple slave units on the network, addressed by P771 – Network Address

To communicate with equipment requiring RS-485 capability, Siemens Milltronics offers the RS-485 External Modem Kit. For more information, go to www.siemens.com/processautomation.

Modbus

The Modbus protocol is supported in the base unit and can be configured using the Communications parameters P770 to P782.

To set up communications with a Modbus RTU master device on port 2 using RS-485, set the following parameters: