For devices connected with the Siemens Milltronics protocol, this parameter is ignored. For devices connected with a serial Modbus slave protocol, this parameter is a number from 1-247. The network administrator must ensure that all devices on the network have unique addresses. Do not use the value 0 for Modbus communications as this is the broadcast address and is inappropriate for a slave device.

P772 Baud Rate

The communication rate with the master device.

Primary Index

Communications Port

 

4.8

 

4800 baud

Values

9.6

 

9600 baud

 

19.2

*

19,200 baud (preset for port 2)

 

115.2

*

115,200 baud (preset for port 1)

This specifies the rate of communication in Kbaud. Any value may be entered, but the only values supported are those shown above. The baud rate should reflect the speed of the connected hardware and protocol used.

P773 Parity

The serial port parity.

Primary Index

Communications Port

 

0

*

No Parity

Values

1

 

Odd Parity

 

2

 

Even Parity

Ensure that the communications parameters are identical between the MultiRanger and all connected devices, as many modems default to N-8-1.

P774 Data Bits

The number of data bits per character.

Primary Index

Communications Port

 

Range: 5 to 8

 

 

8

*

Modbus RTU

Values

7 or 8

 

Modbus ASCII

 

7 or 8

 

Dolphin Plus

P775 Stop Bits

The number of bits between the data bits.

Primary Index

Communications Port

Values

Range: 1 or 2

 

1

* Preset