7ML19981FB06 MultiRanger 100/200 – INSTRUCTION MANUAL Page 95
mmmmm
Comms Installation
For devices connected with the Siemens Milltronics protocol, this parameter is ignored.
For devices connected with a serial Modbus slave protocol, this parameter is a number
from 1-247. The network administrator must ensure that all devices on the network have
unique addresses. Do not use the value 0 for Modbus communications as this is the
broadcast address and is inappropriate for a slave device.
P772 Baud Rate

The communication rate with the master device.

This specifies the rate of communication in Kbaud. Any value may be entered, but the
only values supported are those shown above. The baud rate should reflect the speed of
the connected hardware and protocol used.
P773 Parity

The serial port parity.

Ensure that the communications parameters are identical between the MultiRanger and
all connected devices, as many modems default to N-8-1.
P774 Data Bits

The number of data bits per character.

P775 Stop Bits

The number of bits between the data bits.

Primary Index Communications Port
Values
4.8 4800 baud
9.6 9600 baud
19.2 * 19,200 baud (preset for port 2)
115.2 * 115,200 baud (preset for port 1)
Primary Index Communications Port
Values
0*No Parity
1Odd Parity
2Even Parity
Primary Index Communications Port
Values
Range: 5 to 8
8*Modbus RTU
7 or 8 Modbus ASCII
7 or 8 Dolphin Plus
Primary Index Communications Port
Values Range: 1 or 2
1 * Preset