P113 Relay OFF Setpoint

Sets the process point at which the relay returns to its NORMAL state.

Primary Index

Relay

Values

Range: -999 to 9999

 

 

Preset: ----

 

Altered by

P007 Span

 

P100 Preset Applications

Related

P111 Relay Control Function

 

P112 Relay ON Setpoint

 

 

 

For most applications, the relay is reset at this point. For IN-BOUNDS and OUT-OF- BOUNDS alarms, it is the low point in the specified range. This parameter is set to Span (P007), even when another reading, such as volume, is shown on the LCD.

P115 Relay Interval Setpoint [MR 200]

The length of time in hours between starts.

Primary Index

Relay

Values

Range: 0 to 9000 hours

 

 

Preset: 0.000

 

Altered by

P100 Preset Applications

Related

P111 Relay Control Function

 

 

 

P116 Dead Band [MR 200]

The distance above and below the bound alarm setpoints.

Primary Index

Relay

 

Values

Range: 0.000 to Span Value (P007), or equivalent depending on units

 

 

 

Preset: 2% of span

 

 

P111 Relay Control Function

Related

P112

Relay ON Setpoint

 

P113

Relay OFF Setpoint

 

 

 

 

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 137

Parameters

Page 147
Image 147
Siemens 200 instruction manual P113 Relay OFF Setpoint, P115 Relay Interval Setpoint MR, P116 Dead Band MR