Relay Failsafe is only available for the following relay functions (P111) and is not used for any other relay control function.

 

Relay Function (P111)

Preset (P129)

 

 

 

1

– level alarm

 

 

 

 

2

– in bounds alarm

 

 

 

 

3

– out of bounds alarm

OFF

 

 

 

4

– rate of change alarm

 

 

 

 

5

– temperature alarm

 

 

 

50 to 56 – all pump controls

dE

 

 

 

To select an independent Relay Failsafe value:

1.Press FUNCTION to display the Auxiliary Function symbol.

2.Press ARROWS to scroll through the failsafe options.

3.Select option and press ENTER .

Advanced Pump Control Modifiers (P130 to P137) [MR 200]

Please note that these parameters apply to the MultiRanger 200 only. These parameters only affect relays set to pump operation (P111 = 50 to 56).

P130 Pump Run-On Interval [MR 200]

Sets the number of hours between pump run-on occurrences.

Primary Index

Global

 

 

Values

Range: 0.000 to 1000

 

 

 

Preset: 0.000

 

 

 

Related

Advanced Pump Control Modifiers (P130 to P136)

 

 

 

To clear sediment in a pump-downwet well, run the pump after the normal OFF setpoint is reached to force some solid material through. This parameter sets the time between such events. Only the last pump running can run-on.

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 141

Parameters

Page 151
Image 151
Siemens 200 Advanced Pump Control Modifiers P130 to P137 MR, P130 Pump Run-On Interval MR, Relay Function P111 Preset P129