P007 Span

Sets the range levels to be measured.

Primary Index

Level

Values

Range: 0.000 to 99.000 m (or equivalent depending on units)

 

 

Preset: based on Empty (P006)

 

 

P605 Zero Head

Alters

P112 Relay ON Setpoint

 

P113 Relay OFF Setpoint

Altered By

P005 Units

P006 Empty

 

 

Volume (P050 to P055)

 

P800 Near Blanking

Related

P921 Material Measurement

 

P922 Space Measurement

 

P926 Head Measurement

 

 

 

Span is preset for a value close to the maximum available. Enter a value reflecting maximum application range.

Always prevent the monitored surface from approaching within 0.3 m (1 ft) of the transducer face as this is the minimum blanking for most Siemens Milltronics transducers (some require more blanking – see your transducer manual).

Many other parameters are set as a percentage of span (even if they are entered in units). The values of these other parameters may change if the span is altered after installation and the other parameters are measured using a level determined upward from the Empty level toward the transducer face.

MultiRanger 200

All volumes are based on span so it should be set for the maximum volume point if volume calculations are needed.

Volume (P050 to P055) [MR 200]

Please note that the volume parameters apply only to the MultiRanger 200.

Use these parameters to enable the MultiRanger to show readings based on vessel or wet well volume (rather than level)..

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 123